Description
Clamp-on Ground Resistance Meter Tester DY1200 Earth Ground Resistance Testers
DY1200 Clamp-on Ground Resistance Tester
Main Features:
55*32mm jaw size for larger ground rods
Autoranging ground resistance measurements from 0.01Ohm to 1000Ohm with 0.01Ohm resolution
AC Leakage current range of 10mA to 30.00A with 50µA resolution
Configurable alarm value for resistance and current to support your measurement
Ergonomic mold, full rubber coating for slip proof
Simplifies ground resistance measurements on multiple point ground systems
Verification resistor confirm accuracy of meter
Datalogging with 99 data points
Complete with heavy duty case and verification resistor
Specifications:
Earth Ground Resistance | Range | Resolution | Precision |
0.01Ω ~ 0.99Ω | 0.01Ω | ±1%+0.01Ω | |
1.0Ω ~ 49.9Ω | 0.1Ω | ±1.5%+0.1Ω | |
50.0Ω ~ 99.5Ω | 0.5Ω | ±2%+0.5Ω | |
100Ω ~ 199Ω | 1Ω | ±3%+1Ω | |
200Ω ~ 395Ω | 5Ω | ±6%+5Ω | |
400Ω ~ 590Ω | 10Ω | ±10%+10Ω | |
600Ω ~ 1000Ω | 20Ω | ±20%+20Ω | |
Min. Resolution | 0.01Ω | ||
Configurable alarm value of resistance | 0~199Ω | ||
Leakage current | Range | Resolution | Precision |
0 ~ 80mA | 50µA | ±2.5%+1mA | |
80mA ~ 650mA | 0.5mA | ±2.5%+2mA | |
650mA ~ 4A | 5mA | ±2.5%+10mA | |
4A ~ 30A | 10mA | ±2.5%+20mA | |
Min. Resolution | 50µA | ||
Measurement of leakage current | 46 ~ 65 Hz, RMS | ||
Configurable alarm value of current | 0~499mA | ||
Memory | 99 sets | ||
Conductor Size | 32 * 55 mm | ||
Working Temperature | -10°C ~ 55°C | ||
Working Humidity | 10%~80% | ||
LCD Size | 28.5 x 47 mm |
General Characteristics:
Power: AA1.5x4 (Not included battery)
Product Size: 285*90*60 mm
Product Net Weight: 1285g (Not including battery)
Standard Accessories: Verification resistor, carry case
Standard Individual packing: carry case
Payment & Security
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.